www.testfreaks.com

Reviews, reviews, reviews...

Tripp-lite-suint3000rtxl2u.33946646

Tripp-Lite SUINT3000RTXL2U

3000VA / 3kVA / 2500 watt on-line, double-conversion UPS system Read more

Best Price at Amazon

Specifications

Feature
Value
Comment
OUTPUT
Output Volt Amp Capacity (VA)
3000
Output kVA capacity (kVA)
3
Output Watt Capacity (watts)
2500
Output kW capacity
2.5
Output power factor
0.8
Output Capacity Details
Max output is 3000VA / 2400W at 200, 208, 220V nominal settings
Crest Factor
3:1
Nominal Output Voltage(s) Supported
200v; 208v; 220v; 230v; 240v
Nominal Voltage details
230V default
Frequency compatibility
50 / 60 Hz
Frequency compatibility details
Output frequency matches input nominal on startup, defaults to 50 Hz on cold-start. Frequency conversion from 60 to 50 Hz -or- 50 to 60 Hz supported. Output capacity de-rates by 20% during frequency conversion operation.
Output voltage regulation (line mode)
+/- 2%
Output voltage regulation (Economy line mode)
-12%, + 10%
Output voltage regulation (Battery mode)
+/- 2%
Built-in UPS output receptacles
8 C13 outlet(s); 2 C19 outlet(s)
Built-in controllable switched load banks
Two switchable 4 C13 outlet load banks
Basic PDU options
PDUNV
Metered PDU options
PDUMV20HV
Monitored PDU options
PDUMNV20HV (0U / 4 C19, 20 C13 outlets)
Switched PDU options
PDUMV20HVNET
Output AC waveform (AC mode)
Sine wave
Output AC waveform (battery mode)
Pure Sine wave
INPUT
Rated input current (at maximum load)
15A (200V); 14.4A (208V); 13.6A (220V); 13A (230V); 12.5A (240V)
Nominal Input Voltage(s) Supported
200V AC; 208V AC; 220V AC; 230V AC; 240V AC
Nominal input voltage description
230V factory configuration
UPS input connection type
C20 inlet
UPS Input cord length (ft.)
10 ft / 3m (C19 to C20)
BATTERY
Full load runtime (minutes)
6 min. (2500w)
Half load runtime (minutes)
15 min. (1250w)
Expandable battery runtime
Supports extended runtime with optional external battery packs
External battery pack compatibility
BP72V15-2U
DC system voltage
72V DC
Battery recharge rate (included batteries)
Less than 4.8 hours from 10% to 90%
Replacement battery cartridge (internal UPS battery replacement)
RBC96-2U
Battery Access
Front panel battery access door
Battery replacement description
Hot-swappable, replaceable batteries
VOLTAGE REGULATION
Voltage regulation description
Online, double-conversion power conditioning
Overvoltage correction
2% output voltage regulation during overvoltages to 288
Undervoltage correction
2% output voltage regulation during undervoltages to 160V
Severe undervoltage correction
2% output voltage regulation during undervoltages to 140V (under 66% load only) or 120V (under 33% load only)
LEDS ALARMS & SWITCHES
LED Indicators
14 LEDs indicate line power, online mode, economy/bypass mode, on-battery, overload, battery low, replace battery and fault status information; 4-LED meter displays load and battery charge levels; LED panel rotates for viewing in rack/tower formats
Alarms
Audible alarm indicates power failure, low battery, overload, replace battery and EPO operation
Alarm cancel operation
Power-fail alarm can be silenced using alarm-cancel switch
Switches
2 Switches control off/on power status and alarm-cancel/self-test operation
SURGE / NOISE SUPPRESSION
UPS AC suppression joule rating
420 joules
EMI / RFI AC noise suppression
Yes
AC suppression response time
Instantaneous
PHYSICAL
Installation form factors supported with included accessories
4 post 19 inch rackmount (mounting rail kit included)
Installation form factors supported with optional accessories
2 post rackmount (2POSTRMKITWM); Wallmount (2POSTRMKITWM); Tower (2-9USTAND)
Primary form factor
Rackmount
UPS / Power Module dimensions in primary form factor (height x width x depth / inches)
3.5 x 17.3 x 26
UPS / Power Module dimensions in primary form factor (height x width x depth / cm)
8.9 x 43.9 x 66
Installed whole system total rack space height (rack spaces)
2U
Secondary form factor
Tower (requires
Installed whole system dimensions in secondary form factor (height x width x depth / inches)
17.3 x 3.5 x 26
UPS dimensions in secondary form factor (height x width x depth / cm)
43.9 x 8.9 x 66
UPS / Power Module weight (lbs)
78.3
UPS / Power Module weight (kg)
35.5
UPS Shipping dimensions (height x width x depth / inches)
9 x 22 x 32.8
UPS Shipping dimensions (height x width x depth / cm)
22.9 x 55.9 x 83.3
Shipping weight (lbs)
78.3
Shipping weight (kg)
35.5
UPS housing material
Steel
Cooling method
Fan
ENVIRONMENTAL
Operating Temperature Range
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity
0 to 95%, non-condensing
AC mode BTU / hr. (full load)
1000
AC economy mode BTU / hr. (full load)
241
Battery mode BTU / hr. (full load)
1500
AC economy mode efficiency rating (100% load)
97%
COMMUNICATIONS
Communications interface
USB (HID enabled); DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface
Network monitoring port description
Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure communications
PowerAlert software
Included
Communications cable
USB and DB9 cabling included
WatchDog compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
LINE / BATTERY TRANSFER
Transfer time
No transfer time (0 ms.) in online, double-conversion mode
Low voltage transfer to battery power (setpoint)
160V (100% load), 140V (66% load), 120V (33% load)
High voltage transfer to battery power (setpoint)
288V
SPECIAL FEATURES
Cold Start (startup in battery mode during a power failure)
Cold-start operation supported
High availability UPS features
Automatic inverter bypass; Hot swappable batteries
Green & high efficiency features
High efficiency economy mode operation; Individually controllable load banks; Schedulable daily hours of economy mode operation; Online, double-conversion UPS with precision output voltage regulation
CERTIFICATIONS
UPS Certifications
Tested to UL1778 (USA); Tested to CSA (Canada); Tested to CE (EU); Meets FCC Part 15 Category A (EMI); TAA Compliant
WARRANTY
Product Warranty Period (U.S., Canada & Puerto Rico)
2 years
Release Date
First seen
20 January 2012