www.testfreaks.com

Reviews, reviews, reviews...

Tripp-lite-su5000rt4utf.33946644

Tripp-Lite su5000rt4utf

Tripp Lite E-series SU5000RT4UTF 5000VA / 5kVA / 4500 watt on-li Read more

Best Price at Amazon

Specifications

Feature
Value
Comment
OUTPUT
Output Volt Amp Capacity (VA)
5000
Output kVA capacity (kVA)
5.0
Output Watt Capacity (watts)
4500
Output kW capacity
4.5
Output power factor
0.9
Crest Factor
3:1
Nominal Output Voltage(s) Supported
120v; 208v
Frequency compatibility
50/60 Hz (auto-selectable)
Output voltage regulation (line mode)
+/- 2%
Output voltage regulation (Economy line mode)
+/- 10%
Output voltage regulation (Battery mode)
+/- 2%
Built-in UPS output receptacles
12 5-15/20R outlet(s); 2 L6-20R outlet(s); 2 L6-30R outlet(s)
Output circuit breaker
High voltage 20A breaker protects L6-20R outlets, L6-30R outlets are unbreakered; Low voltage 20A breakers protect 3 5-15/20R outlets each
Basic PDU options
PDU1220
Metered PDU options
PDUMH20
Monitored PDU options
PDUMNV20 (0U / 24 5-15/20R outlets); PDUMNV20HV (0U / 4 C19, 20 C13 outlets); PDUMNV30HV (0U / 4 C19, 20 C13 outlets); PDUMNH20 (1U / 16 5-15/20R outlets)
Switched PDU options
PDUMH20ATNET
Output AC waveform (AC mode)
Pure sine wave
Output AC waveform (battery mode)
Pure Sine wave
INPUT
Rated input current (at maximum load)
24A (208V)
Nominal Input Voltage(s) Supported
208V AC
UPS input connection type
L6-30P
UPS Input cord length (ft.)
10
UPS Input cord length (m)
3
Recommended Electrical Service
30A
BATTERY
Full load runtime (minutes)
3.5 minutes (4500w)
Half load runtime (minutes)
11 minutes (2250w)
Expandable battery runtime
Supports extended runtime with optional external battery packs
External battery pack compatibility
BP192V12-3U
DC system voltage
192V DC
Battery recharge rate (included batteries)
6 hours (from 10% to 90%)
Replacement battery cartridge (internal UPS battery replacement)
RBC5-192 (qty 1)
Battery Access
Front panel battery access door
Battery replacement description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage regulation description
Online, double-conversion power conditioning
Overvoltage correction
2% output voltage regulation during overvoltages to 280V (full load) / 300V (90% load or less)
Undervoltage correction
2% output voltage regulation during undervoltages to 156V (full load) / 100V (50% load or less)
LEDS ALARMS & SWITCHES
LED Indicators
6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD screen offers additional information and control options
Front panel LCD display
Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options; LED/LCD panel rotates for viewing in rack/tower formats (see manual)
Alarms
Unique audible alarms for all major UPS, environmental and power conditions (see manual)
Alarm cancel operation
Alarm cancel switch
Switches
2 Switches control off/on power status and alarm-cancel/self-test operation; 2 additional switches support set and execute scrolling LCD functions
SURGE / NOISE SUPPRESSION
UPS AC suppression response time
Instantaneous
EMI / RFI AC noise suppression
Yes
PHYSICAL
Installation form factors supported with included accessories
4 post 19 inch rackmount (mounting kit included)
Included mounting accessory description
2 sets of adjustable 4 post rack rails included
Installation form factors supported with optional accessories
2 post rackmount (2POSTRMKITWM); Tower (2-9USTAND)
Optional mounting accessory notes
2 sets of
Primary form factor
Rackmount
UPS / Power Module dimensions in primary form factor (height x width x depth / inches)
6.85 x 17.5 x 20.7
UPS / Power Module dimensions in primary form factor (height x width x depth / cm)
17.4 x 44.5 x 52.6
Installed whole system maximum rack depth (inches)
20.75
Installed whole system maximum rack depth (cm)
52.7
Installed whole system total rack space height (rack spaces)
6U
Secondary form factor
Tower
UPS / Power Module weight (lbs)
113.6
UPS / Power Module weight (kg)
51.6
Stepdown transformer dimensions (height x width x depth / inches)
3.5 x 17.5 x 20.75
Stepdown transformer dimensions (height x width x depth / cm)
8.8 x 44.4 x 52.7
Stepdown transformer weight (lbs)
76
Stepdown transformer weight (kg)
34.5
UPS Shipping dimensions (height x width x depth / inches)
22 x 25 x 30
UPS Shipping dimensions (height x width x depth / cm)
55.9 x 63.5 x 76.2
Shipping weight (lbs)
278
Shipping weight (kg)
126.2
UPS housing material
Sheet metal
Cooling method
Fan
ENVIRONMENTAL
Operating Temperature Range
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range
5 to 122 F / -15 to 50 C
Relative Humidity
5% to 90% (non-condensing)
AC mode BTU / hr. (full load)
1767
AC economy mode BTU / hr. (full load)
638
Battery mode BTU / hr. (full load)
1700
AC economy mode efficiency rating (100% load)
96%
Operating Elevation (ft)
0 to 6560 ft. / 0 to 2000 m
Audible Noise
65 dB at 1m front side
COMMUNICATIONS
Communications interface
USB (HID enabled); DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface
Network monitoring port description
Two contact closure monitoring options available - RELAYIOCARD with six configurable contact closure outputs (uses UPS card slot) and RELAYIOMINI with 3 configurable contact closure outputs (requires removal of USB port module)
PowerAlert software
Included
Communications cable
USB, DB9 serial and EPO cables included
WatchDog compatibility
Yes
LINE / BATTERY TRANSFER
Transfer time
No transfer time (0 ms.) in online, double-conversion mode
Low voltage transfer to battery power (setpoint)
156V (full load) / 100V (50% load or less, derates linearly)
High voltage transfer to battery power (setpoint)
280V (full load) / 300V (90% load or less)
SPECIAL FEATURES
Cold Start (startup in battery mode during a power failure)
Cold-start operation supported
High availability UPS features
Automatic inverter bypass; Hot swappable batteries
Green & high efficiency features
High efficiency economy mode operation; Support for daily startup and shutoff; Schedulable daily hours of economy mode operation
CERTIFICATIONS
UPS Certifications
Tested to UL1778 (USA); Tested to CSA (Canada); Meets FCC Part 15 Category B (EMI); ROHS (Restriction of Hazardous Substances)
UPS Certification details
IEC 61000-4-5 1995 B Surge Immunity
WARRANTY
Product Warranty Period (U.S., Canada & Puerto Rico)
2 years
Connected Equipment Insurance (U.S., Canada & Puerto Rico)
$250,000 connected equipment insurance
Release Date
First seen
20 January 2012