www.testfreaks.com

Reviews, reviews, reviews...

Tripp-lite-su1000rtxl2ua.33655484

Tripp-Lite SU1000RTXL2Ua

1000VA on-line, double-conversion UPS system for critical server Read more

Best Price at Amazon

Specifications

Feature
Value
Comment
OUTPUT
Output Volt Amp Capacity (VA)
1000
Output kVA capacity (kVA)
1
Output Watt Capacity (watts)
800
Output power factor
0.8
Crest Factor
3:1
Nominal Output Voltage(s) Supported
100v; 110v; 120v
Nominal Voltage details
120V default
Frequency compatibility
50 / 60 Hz
Frequency compatibility details
Output frequency matches input nominal on startup, defaults to 60 Hz on cold-start
Output voltage regulation (line mode)
+/- 2%
Output voltage regulation (Economy line mode)
+/- 10%
Output voltage regulation (Battery mode)
+/- 2%
Built-in UPS output receptacles
6 5-15R outlet(s)
Built-in controllable switched load banks
Two switchable single-outlet 5-15R load banks
Basic PDU options
PDU1215
Metered PDU options
PDUMH15
Switched PDU options
PDUMH15ATNET
External PDU redundancy options
*ATS switch options
Output AC waveform (AC mode)
Sine wave
Output AC waveform (battery mode)
Sine wave
INPUT
Rated input current (at maximum load)
8.6A
Nominal Input Voltage(s) Supported
100V AC; 110V AC; 120V AC
UPS input connection type
5-15P
Input circuit breaker
15A
UPS Input cord length (ft.)
10
UPS Input cord length (m)
3
Recommended Electrical Service
15A 120V
BATTERY
Full load runtime (minutes)
4.5 min. (800w)
Half load runtime (minutes)
14 min. (400w)
Expandable battery runtime
Extended runtime supported via optional external battery packs
External battery pack compatibility
BP24V15RT2U
DC system voltage
24V DC
Battery recharge rate (included batteries)
Less than 6 hours from 10% to 80%
Replacement battery cartridge (internal UPS battery replacement)
RBC92-2U
Battery Access
Front panel battery access door
Battery replacement description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage regulation description
Online, double-conversion power conditioning
Overvoltage correction
2% output voltage regulation during overvoltages to 150
Undervoltage correction
2% output voltage regulation during undervoltages to 80
Severe undervoltage correction
2% output voltage regulation during undervoltages to 65 (under 70% load only)
LEDS ALARMS & SWITCHES
LED Indicators
14 LEDs indicate line power, online mode, economy/bypass mode, on-battery, overload, battery low, replace battery and fault status information; 4-LED meter displays load and battery charge levels; LED panel rotates for viewing in rack/tower formats
Alarms
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
Alarm cancel operation
Power-fail alarm can be silenced using alarm-cancel switch
Switches
2 switches control off/on power status and alarm-cancel/self-test operation
SURGE / NOISE SUPPRESSION
UPS AC suppression joule rating
510
UPS AC suppression response time
Instantaneous
UPS Dataline suppression
1 line TEL / DSL or 10Base T Ethernet protection
EMI / RFI AC noise suppression
Yes
PHYSICAL
Installation form factors supported with included accessories
4 post 19 inch rackmount (mounting rail kit included)
Installation form factors supported with optional accessories
2 post rackmount (2POSTRMKITWM); Wallmount (2POSTRMKITWM); Tower (2-9USTAND)
Primary form factor
Rackmount
UPS / Power Module dimensions in primary form factor (height x width x depth / inches)
3.5 x 17.5 x 13.5
UPS / Power Module dimensions in primary form factor (height x width x depth / cm)
8.9 x 44.4 x 34.3
Installed whole system total rack space height (rack spaces)
2U
Secondary form factor
Tower (requires
Installed whole system dimensions in secondary form factor (height x width x depth / inches)
17.5 x 3.5 x 13.5
UPS dimensions in secondary form factor (height x width x depth / cm)
44.4 x 8.9 x 34.3
UPS / Power Module weight (lbs)
29
UPS / Power Module weight (kg)
13.2
UPS Shipping dimensions (height x width x depth / inches)
9.5 x 20 x 24
UPS Shipping dimensions (height x width x depth / cm)
24.1 x 50.8 x 61
Shipping weight (lbs)
41
Shipping weight (kg)
18.6
UPS housing material
Steel
Cooling method
Fan
ENVIRONMENTAL
Operating Temperature Range
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity
0 to 95%, non-condensing
AC mode BTU / hr. (full load)
406.4
AC economy mode BTU / hr. (full load)
173.6
Battery mode BTU / hr. (full load)
442.8
AC economy mode efficiency rating (100% load)
94%
COMMUNICATIONS
Communications interface
USB (HID enabled); DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface
Network monitoring port description
Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure communications
PowerAlert software
Included
Communications cable
USB and DB9 cabling included
WatchDog compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
LINE / BATTERY TRANSFER
Transfer time
No transfer time (0 ms.) in online, double-conversion mode
Low voltage transfer to battery power (setpoint)
80V (100% load), 65V (
High voltage transfer to battery power (setpoint)
150
SPECIAL FEATURES
Cold Start (startup in battery mode during a power failure)
Cold-start operation supported
High availability UPS features
Automatic inverter bypass; Hot swappable batteries
Green & high efficiency features
High efficiency economy mode operation; Individually controllable load banks; Schedulable daily hours of economy mode operation
CERTIFICATIONS
UPS Certifications
Tested to UL1778 (USA); Tested to CSA (Canada); Meets FCC Part 15 Category B (EMI); Meets FCC Part 68 / Industrie Canada (telecommunications); ROHS (Reduction of Hazardous Substances)
WARRANTY
Product Warranty Period (U.S., Canada & Puerto Rico)
2 years
Connected Equipment Insurance (U.S., Canada & Puerto Rico)
$250,000 connected equipment insurance
Release Date
First seen
20 January 2012